Western Reserve Controls WRC-CANR-DF-DN User’s Manual
PUB 14.1
6
Table 4-1 Module Status LED (labeled MS)
LED State Module Status Meaning
OFF No Power There is no power through DeviceNet.
Green
Device Operational WRC-CANR-DF-DN is operating normally.
Flashing Green Device in Standby WRC-CANR-DF-DN is in intialization.
Flashing Red Minor Fault Recoverable fault.
Red Unrecoverable Fault WRC-CANR-DF-DN may be damaged.
Flashing Red/Green Device Self-Testing WRC-CANR-DF-DN is in self-test mode.
Table 4-2 Network Status LEDs (labeled NSA and NSB)
LED State Module Status Meaning
OFF No Power / Not on-line WRC-CANR-DF-DN has no power or device
is not operating.
Flashing Green Autobaud selection The WRC-CANR-DF-DN is waiting for a valid
message to fix the baudrate.
Green
On-line WRC-CANR-DF-DN is operating normally.
Flashing Red Communications error One of several communications errors
(defined below) has occurred.
Red Critical link failure WRC-CANR-DF-DN has detected an error
which makes it incapable of communicating
on the link.
Communications errors include:
• Transmit Check
• Bus Off
• Error Passive
• Warning Level
Table 4-3 Diagnostic Status LEDs (labeled DNG)
LED State Module Status Meaning
OFF No Power / Not on-line Normal operation.
Flashing Green Autobaud selection Waiting for a valid message to select the
baud rate.
Green On-line Not defined.
Flashing Red Communications error The internal FIFO stack has overflowed on
one of the network sides because the other
network could not complete
communications.
Komentarze do niniejszej Instrukcji